Novameta island extraction hoods serve cooking equipment arranged in a central commercial kitchen island. HNCD, HNCA, HPCD and HFCD families include stainless steel cyclonic grease filters. Sizing must account for open-sided air movement, equipment footprint and the heat, grease and vapour loads.
HNCD is the conventional island canopy. HNCA uses a tapered profile for lower ceilings, although its catalogue body height is still 480 mm. HPCD uses capture-assisting air jets, while HFCD combines these with separate low-velocity make-up air supply. Air jets and make-up air are distinct functions.
Check hood overhang on every exposed side, grease filter count and exhaust connection dimensions. The manufacturer recommends at least 300 mm overhang on open sides and 450 mm on the oven-door side. The maximum catalogue airflow is a hood rating, not the specified operating airflow: the exhaust fan, ducting and installation are designed and quoted separately.
Available options depend on the model and may include LED lighting, dampers and joining kits. Refer to each product configuration for included equipment. For cooking equipment installed against a wall, choose a wall canopy hood instead.
Explore related options: professional extraction hoods.
They are intended for installation over an open island cooking station. Suitability depends on the equipment and project.
Check hood overhang around the station and extraction airflow; nominal hood length alone is insufficient.
No. Required airflow depends on the heat, vapour or contaminant load and room ventilation.
Match connection position, diameter, pressure losses and maintenance access to the ventilation design.
In a commercial kitchen, extraction and make-up-air systems work together, so installation should follow a coordinated design.