Product code: MCV-NPD-3069A
Available quantity 4-6 weeks
| Manufacturer: | INTARCON |
INTARCON INTARBLOCK PRO MCV-NPD-3069A is a professional wall-mounted R290 monoblock for chiller cold rooms. R290 is an A3 refrigerant (GWP 0.02). The PRO design emphasizes accessible service components and advanced controls.
| Room temperature | Cooling capacity | Recommended volume |
|---|---|---|
| 0 °C | 4505 W | 62 m³ |
| +5 °C | 5329 W | 100 m³ |
| +10 °C | 6180 W | 180 m³ |
Manufacturer ratings are stated at +35 °C ambient; volumes are indicative only. Verify insulation heat loss, door usage, product heat load and operating conditions before selection.
EC condenser fans, microchannel condenser with protective polyester coating, washable air filter, accessible electrical panel and maintenance components. Hermetic compressor, thermostatic expansion valve, hot-gas defrost and a removable stainless-steel condensate tray.
XM670K controller: advanced programming and energy-saving/defrost cycles, with multi-unit coordination capability where a compatible networking installation is provided. Network cabling and all controls must not be assumed to be included in the base package.
Wall-mounted Drop-in unit, size 3, nominal supply 400 V 3N~ 50 Hz. Confirm the original 2026 catalog p. 277 drawing before cutting insulated wall panels. The H–L dimensions refer to the mounting frame, not verified cut-out dimensions.
| Drawing letter | Dimension |
|---|---|
| A | 906 mm |
| B | 853 mm |
| C | 1101 mm |
| D | 455 mm |
| E | 686 mm |
| F | 455 mm |
| G | 878 mm |
| H | 890 mm |
| I | 56 mm |
| J | 761 mm |
| K | 129 mm |
| L | 560 mm |
Optional accessories include a centrifugal EC condenser fan for ducted heat exhaust, electrical connector kits, suitable voltage protection, a door micro-switch, an electrical supply cable and a single optional 100/150 mm mounting-pad selection. A backdraft damper is suitable only with a duct-compatible fan; verify all dependencies and pressure losses.
R290 is an A3 flammable refrigerant. Installation, electrical connection and service require qualified personnel under the manufacturer's safety and ventilation guidance. Cold-room construction, installation, commissioning and unloading are excluded unless specified. Made to order; lead time 4–6 weeks.
| Capacity and internal fittings | |
|---|---|
| Capacity Cooling Coldroom Units, m³ | 62 |
| Recommended cold-room volume at +0 °C, m³ | 62 |
| Recommended cold-room volume at +10 °C, m³ | 180 |
| Recommended cold-room volume at +5 °C, m³ | 100 |
| Controls and functions | |
|---|---|
| Controller | XM670K |
| Dimensions and weight | |
|---|---|
| Dimensions according to manufacturer drawing | A=906; B=853; C=1101; D=455; E=686; F=455; G=878; H=890; I=56; J=761; K=129; L=560 mm |
| Mounting configuration | Wall-panel Drop-in; verify cut-out on p. 277 drawing |
| Weight, kg | 142 |
| Energy and electrical data | |
|---|---|
| Input Power, W | 3091 |
| Maximum current draw, A | 12.9 |
| Voltage / Frequency, V/Hz | 400 V 3N~ 50 Hz |
| General information | |
|---|---|
| Delivery method | Made to order; lead time 4–6 weeks |
| Mounting type | Wall-mounted |
| Series | INTARBLOCK PRO (CV-NPD) |
| Refrigeration and ventilation system | |
|---|---|
| Condenser airflow with centrifugal fan, m³/h | 3000 |
| Condenser cooling | Air-cooled |
| Defrost Type | Hot-gas defrost |
| Evaporator airflow, m³/h | 2800 |
| Noise Level, dB(A) | 45 (at 10 m) |
| Refrigerant | R290 (A3) |
| Refrigerant Charge, g | less than 500 per circuit |
| Refrigerant GWP | 0.02 |
| Temperature and performance | |
|---|---|
| Cooling capacity at +0 °C, W | 4505 |
| Cooling capacity at +10 °C, W | 6180 |
| Cooling capacity at +5 °C, W | 5329 |
| Temperature group | Positive temperature |
There are no reviews for this product!