Product code: MCV-NN-3034A
Available quantity 4-6 weeks
| Manufacturer: | INTARCON |
INTARCON INTARBLOCK A2L CV-NN MCV-NN-3034A – a wall-mounted refrigeration monoblock for a positive-temperature cold room. Refrigerant R455A is A2L class, global warming potential (GWP) 146. Select by actual heat load, temperature and volume.
| Room temperature | Cooling capacity | Volume |
|---|---|---|
| 0 °C | 2357 W | 28 m³ |
| +5 °C | 2810 W | 46 m³ |
| +10 °C | 3291 W | 75 m³ |
Manufacturer data at +35 °C ambient. Room volumes are indicative and do not substitute for a heat-load assessment.
R455A (A2L) refrigerant, hermetic reciprocating compressor, high-pressure safety switch, thermostatic expansion valve, circuit-breaker protection, hot-gas defrost, condensate management and automatic evaporation, LED cold-room lighting and door micro-switch connection cable. Optional accessory hardware is selected separately.
XW270K controller with remote digital control, min/max temperature recording, Jet Cool and night mode.
Wall-mounted Drop-in installation; A–N mounting frame dimensions are not a validated panel cut-out. Confirm the drawing and panel thickness for this model. Manufacturer size 3, catalog supply 230V I+N ~ 50Hz*. Lettered A–N dimensions refer to the 2026 manufacturer catalog p. 287 installation drawing.
| Reference | Dimension |
|---|---|
| A | 365 mm |
| B | 514 mm |
| C | 122 mm |
| D | 470 mm |
| E | 735 mm |
| F | 940 mm |
| G | 50 mm |
| H | 715 mm |
| I | 475 mm |
| J | 75 mm |
| K | 45 mm |
| L | 607 mm |
| M | 20 mm |
| N | 356 mm |
The standard axial condenser fan is not suited to ducts. For ducted hot-air exhaust select the centrifugal fan (horizontal or vertical discharge on roof models). Up to 20 m equivalent duct length, with each 90° bend equivalent to 5 m. Check duct section and total resistance. Circular-duct adaptor and damper are separate options.
Optional anti-corrosion coating, voltage protection, door switch and Master–Slave adaptation may be selected subject to compatibility.
R455A is A2L-class refrigerant; installation and servicing require qualified personnel. The cold room, installation, commissioning and unloading are excluded unless agreed otherwise. Made to order; lead time 4–6 weeks.
| Capacity and internal fittings | |
|---|---|
| Capacity Cooling Coldroom Units, m³ | 28 |
| Recommended cold-room volume at +0 °C, m³ | 28 |
| Recommended cold-room volume at +10 °C, m³ | 75 |
| Recommended cold-room volume at +5 °C, m³ | 46 |
| Controls and functions | |
|---|---|
| Controller | XW270K |
| Dimensions and weight | |
|---|---|
| Dimensions according to manufacturer drawing | A=365; B=514; C=122; D=470; E=735; F=940; G=50; H=715; I=475; J=75; K=45; L=607; M=20; N=356 mm |
| Mounting configuration | Wall-mounted Drop-in installation; A–N mounting frame dimensions are not a validated panel cut-out. Confirm the drawing and panel thickness for this model. |
| Weight, kg | 101 |
| Energy and electrical data | |
|---|---|
| Input Power, W | 1430 |
| Maximum current draw, A | 20.4 |
| Voltage / Frequency, V/Hz | 230V I+N ~ 50Hz* |
| General information | |
|---|---|
| Delivery method | Made to order; lead time 4–6 weeks |
| Mounting type | Wall-mounted |
| Series | INTARBLOCK A2L CV-NN |
| Refrigeration and ventilation system | |
|---|---|
| Condenser cooling | Air-cooled |
| Defrost Type | Hot-gas defrost |
| Evaporator airflow, m³/h | 1100 |
| Noise Level, dB(A) | 38 (at 10 m) |
| Refrigerant | R455A (A2L) |
| Refrigerant Charge, g | less than 2000 |
| Refrigerant GWP | 146 |
| Temperature and performance | |
|---|---|
| Cooling capacity at +0 °C, W | 2357 |
| Cooling capacity at +10 °C, W | 3291 |
| Cooling capacity at +5 °C, W | 2810 |
| Temperature group | Positive temperature |
There are no reviews for this product!