Product code: MCV-LD-2034A
Available quantity 4-6 weeks
| Manufacturer: | INTARCON |
INTARCON INTARBLOCK R290 MCV-LD-2034A is a compact wall-mounted refrigeration monoblock for a positive-temperature cold room. It uses R290 (propane), an A3-class refrigerant with GWP 0.02. Select capacity according to actual heat loads, required temperature and room volume.
| Room temperature | Cooling capacity | Recommended volume |
|---|---|---|
| 0 °C | 2215 W | 27 m³ |
| +5 °C | 2618 W | 43 m³ |
| +10 °C | 2960 W | 70 m³ |
Manufacturer ratings refer to +35 °C ambient temperature. Room volumes are indicative; insulation, door opening and product heat loads influence final sizing.
Hermetic reciprocating compressor, EC electronically controlled fans, high and low pressure switches, thermostatic expansion valve, hot-gas defrost, stainless-steel condensate tray and automatic condensate evaporation. Integrated LED cold-room lighting, door micro-switch and removable through-wall insulation pad.
XW60LH electronic controller: temperature min/max recording, Jet Cool rapid-cooling function, night operating mode and relays for compressor, fan, defrost and lighting.
Plug-in installation through the wall panel. Manufacturer size 2; letter references A–H in the drawing denote equipment geometry, not an automatically validated wall cut-out. Confirm the original p. 281 installation drawing and panel thickness before cutting. Source: IMPAFRI / INTARCON 2026 catalog, pp. 280–281.
| Drawing reference | Dimension |
|---|---|
| A | 620 mm |
| B | 764 mm |
| C | 343 mm |
| D | 106 mm |
| E | 310 mm |
| F | 676 mm |
| G | 600 mm |
| H | 680 mm |
Optional factory coatings: epoxy anti-corrosion treatment for the evaporator heat exchanger and polyurethane anti-corrosion treatment for the condenser heat exchanger. They are optional price supplements, not part of the standard unit.
R290 is an A3-class refrigerant. Installation, electrical wiring and servicing must be performed by qualified technicians in line with the manufacturer's safety and ventilation requirements. The cold room, installation, commissioning and unloading are excluded unless stated otherwise. Made to order; lead time 4–6 weeks.
| Capacity and internal fittings | |
|---|---|
| Capacity Cooling Coldroom Units, m³ | 27 |
| Recommended cold-room volume at +0 °C, m³ | 27 |
| Recommended cold-room volume at +10 °C, m³ | 70 |
| Recommended cold-room volume at +5 °C, m³ | 43 |
| Controls and functions | |
|---|---|
| Controller | XW60LH |
| Dimensions and weight | |
|---|---|
| Dimensions according to manufacturer drawing | A=620; B=764; C=343; D=106; E=310; F=676; G=600; H=680 mm |
| Mounting configuration | Plug-in through-wall; verify cut-out on p. 281 drawing |
| Weight, kg | 86 |
| Energy and electrical data | |
|---|---|
| Input Power, W | 1310 |
| Maximum current draw, A | 9.0 |
| Voltage / Frequency, V/Hz | 230 V 1N~ 50 Hz |
| General information | |
|---|---|
| Delivery method | Made to order; lead time 4–6 weeks |
| Mounting type | Wall-mounted |
| Series | INTARBLOCK R290 (CV-LD) |
| Refrigeration and ventilation system | |
|---|---|
| Condenser cooling | Air-cooled |
| Defrost Type | Hot-gas defrost |
| Evaporator airflow, m³/h | 950 |
| Noise Level, dB(A) | 35 (at 10 m) |
| Refrigerant | R290 (A3) |
| Refrigerant Charge, g | less than 200 |
| Refrigerant GWP | 0.02 |
| Temperature and performance | |
|---|---|
| Cooling capacity at +0 °C, W | 2215 |
| Cooling capacity at +10 °C, W | 2960 |
| Cooling capacity at +5 °C, W | 2618 |
| Temperature group | Positive temperature |
There are no reviews for this product!