Manufacturer: INTARCON

INTARCON INTARBLOCK R290 MCV-LD-0009A is a compact wall-mounted refrigeration monoblock for a positive-temperature cold room. It uses R290 (propane), an A3-class refrigerant with GWP 0.02. Select capacity according to actual heat loads, required temperature and room volume.

Cooling capacity and recommended cold-room volume

Room temperatureCooling capacityRecommended volume
0 °C635 W5 m³
+5 °C740 W7 m³
+10 °C850 W12 m³

Manufacturer ratings refer to +35 °C ambient temperature. Room volumes are indicative; insulation, door opening and product heat loads influence final sizing.

Standard equipment

Hermetic reciprocating compressor, EC electronically controlled fans, high and low pressure switches, thermostatic expansion valve, hot-gas defrost, stainless-steel condensate tray and automatic condensate evaporation. Integrated LED cold-room lighting, door micro-switch and removable through-wall insulation pad.

XW60LH electronic controller: temperature min/max recording, Jet Cool rapid-cooling function, night operating mode and relays for compressor, fan, defrost and lighting.

Installation and dimensions

Plug-in installation through the wall panel. Manufacturer size 0; letter references A–H in the drawing denote equipment geometry, not an automatically validated wall cut-out. Confirm the original p. 281 installation drawing and panel thickness before cutting. Source: IMPAFRI / INTARCON 2026 catalog, pp. 280–281.

Drawing referenceDimension
A420 mm
B803 mm
C237 mm
D86 mm
E207 mm
F596 mm
G400 mm
H600 mm

Optional accessories

Optional factory coatings: epoxy anti-corrosion treatment for the evaporator heat exchanger and polyurethane anti-corrosion treatment for the condenser heat exchanger. They are optional price supplements, not part of the standard unit.

Safety and delivery

R290 is an A3-class refrigerant. Installation, electrical wiring and servicing must be performed by qualified technicians in line with the manufacturer's safety and ventilation requirements. The cold room, installation, commissioning and unloading are excluded unless stated otherwise. Made to order; lead time 4–6 weeks.

Capacity and internal fittings
Capacity Cooling Coldroom Units, m³ 5
Recommended cold-room volume at +0 °C, m³ 5
Recommended cold-room volume at +10 °C, m³ 12
Recommended cold-room volume at +5 °C, m³ 7
Controls and functions
Controller XW60LH
Dimensions and weight
Dimensions according to manufacturer drawing A=420; B=803; C=237; D=86; E=207; F=596; G=400; H=600 mm
Mounting configuration Plug-in through-wall; verify cut-out on p. 281 drawing
Weight, kg 38
Energy and electrical data
Input Power, W 400
Maximum current draw, A 3.5
Voltage / Frequency, V/Hz 230 V 1N~ 50 Hz
General information
Delivery method Made to order; lead time 4–6 weeks
Mounting type Wall-mounted
Series INTARBLOCK R290 (CV-LD)
Refrigeration and ventilation system
Condenser cooling Air-cooled
Defrost Type Hot-gas defrost
Evaporator airflow, m³/h 300
Noise Level, dB(A) 29 (at 10 m)
Refrigerant R290 (A3)
Refrigerant Charge, g less than 100
Refrigerant GWP 0.02
Temperature and performance
Cooling capacity at +0 °C, W 635
Cooling capacity at +10 °C, W 850
Cooling capacity at +5 °C, W 740
Temperature group Positive temperature