• English
  • Lithuanian
excl VAT

INTARCON BCV-NPD-1018A INTARBLOCK PRO wall-mounted R290 monoblock, 584 W

Product code: BCV-NPD-1018A

Available quantity 4-6 weeks

INTARCON INTARBLOCK PRO BCV-NPD-1018A, R290, freezer room. Wall-mounted, 584 W at −20 °C, up to 3 m³ at +35 °C ambient. XM670K, service-oriented design; made to order.
€3,56050 inc VAT
€2,94256 excl VAT
Have any questions about this item? Ask
Manufacturer: INTARCON

INTARCON INTARBLOCK PRO BCV-NPD-1018A is a professional wall-mounted R290 monoblock for freezer cold rooms. R290 is an A3 refrigerant (GWP 0.02). The PRO design emphasizes accessible service components and advanced controls.

Cooling capacity and recommended room size

Room temperatureCooling capacityRecommended volume
-25 °C469 W1 m³
-20 °C584 W3 m³
-15 °C706 W5 m³

Manufacturer ratings are stated at +35 °C ambient; volumes are indicative only. Verify insulation heat loss, door usage, product heat load and operating conditions before selection.

PRO standard equipment

EC condenser fans, microchannel condenser with protective polyester coating, washable air filter, accessible electrical panel and maintenance components. Hermetic compressor, thermostatic expansion valve, hot-gas defrost and a removable stainless-steel condensate tray.

XM670K controller: advanced programming and energy-saving/defrost cycles, with multi-unit coordination capability where a compatible networking installation is provided. Network cabling and all controls must not be assumed to be included in the base package.

Installation and dimensions

Wall-mounted Drop-in unit, size 1, nominal supply 230 V 1N~ 50 Hz. Confirm the original 2026 catalog p. 277 drawing before cutting insulated wall panels. The H–L dimensions refer to the mounting frame, not verified cut-out dimensions.

Drawing letterDimension
A556 mm
B853 mm
C1023 mm
D390 mm
E693 mm
F348 mm
G468 mm
H448 mm
I56 mm
J341 mm
K129 mm
L450 mm

Factory accessories

Optional accessories include a centrifugal EC condenser fan for ducted heat exhaust, electrical connector kits, suitable voltage protection, a door micro-switch, an electrical supply cable and a single optional 100/150 mm mounting-pad selection. A backdraft damper is suitable only with a duct-compatible fan; verify all dependencies and pressure losses.

Safety and delivery

R290 is an A3 flammable refrigerant. Installation, electrical connection and service require qualified personnel under the manufacturer's safety and ventilation guidance. Cold-room construction, installation, commissioning and unloading are excluded unless specified. Made to order; lead time 4–6 weeks.

Capacity and internal fittings
Capacity Cooling Coldroom Units, m³ 3
Recommended cold-room volume at −15 °C, m³ 5
Recommended cold-room volume at −20 °C, m³ 3
Recommended cold-room volume at −25 °C, m³ 1
Controls and functions
Controller XM670K
Dimensions and weight
Dimensions according to manufacturer drawing A=556; B=853; C=1023; D=390; E=693; F=348; G=468; H=448; I=56; J=341; K=129; L=450 mm
Mounting configuration Wall-panel Drop-in; verify cut-out on p. 277 drawing
Weight, kg 72
Energy and electrical data
Input Power, W 588
Maximum current draw, A 5.8
Voltage / Frequency, V/Hz 230 V 1N~ 50 Hz
General information
Delivery method Made to order; lead time 4–6 weeks
Mounting type Wall-mounted
Series INTARBLOCK PRO (CV-NPD)
Refrigeration and ventilation system
Condenser airflow with centrifugal fan, m³/h 1450
Condenser cooling Air-cooled
Defrost Type Hot-gas defrost
Evaporator airflow, m³/h 750
Noise Level, dB(A) 43 (at 10 m)
Refrigerant R290 (A3)
Refrigerant Charge, g less than 150 per circuit
Refrigerant GWP 0.02
Temperature and performance
Cooling capacity at −15 °C, W 706
Cooling capacity at −20 °C, W 584
Cooling capacity at −25 °C, W 469
Temperature group Negative temperature

There are no reviews for this product!

Write