INTARCON INTARBLOCK A2L CV-NN BCV-NN-2034A – a wall-mounted refrigeration monoblock for a freezer cold room. Refrigerant R455A is A2L class, global warming potential (GWP) 146. Select by actual heat load, temperature and volume.
| Room temperature | Cooling capacity | Volume |
|---|---|---|
| -25 °C | 848 W | 5 m³ |
| -20 °C | 1065 W | 9 m³ |
| -15 °C | 1303 W | 15 m³ |
Manufacturer data at +35 °C ambient. Room volumes are indicative and do not substitute for a heat-load assessment.
R455A (A2L) refrigerant, hermetic reciprocating compressor, high-pressure safety switch, thermostatic expansion valve, circuit-breaker protection, hot-gas defrost, condensate management and automatic evaporation, LED cold-room lighting and door micro-switch connection cable. Optional accessory hardware is selected separately.
XW270K controller with remote digital control, min/max temperature recording, Jet Cool and night mode.
Wall-mounted Drop-in installation; A–N mounting frame dimensions are not a validated panel cut-out. Confirm the drawing and panel thickness for this model. Manufacturer size 2, catalog supply 230V I+N ~ 50Hz. Lettered A–N dimensions refer to the 2026 manufacturer catalog p. 287 installation drawing.
| Reference | Dimension |
|---|---|
| A | 340 mm |
| B | 514 mm |
| C | 122 mm |
| D | 330 mm |
| E | 620 mm |
| F | 920 mm |
| G | 140 mm |
| H | 600 mm |
| I | 335 mm |
| J | 75 mm |
| K | 30 mm |
| L | 522 mm |
| M | 16 mm |
| N | 218 mm |
The standard axial condenser fan is not suited to ducts. For ducted hot-air exhaust select the centrifugal fan (horizontal or vertical discharge on roof models). Up to 20 m equivalent duct length, with each 90° bend equivalent to 5 m. Check duct section and total resistance. Circular-duct adaptor and damper are separate options.
Optional anti-corrosion coating, voltage protection, door switch and Master–Slave adaptation may be selected subject to compatibility.
R455A is A2L-class refrigerant; installation and servicing require qualified personnel. The cold room, installation, commissioning and unloading are excluded unless agreed otherwise. Made to order; lead time 4–6 weeks.
| Capacity and internal fittings | |
|---|---|
| Capacity Cooling Coldroom Units, m³ | 9 |
| Recommended cold-room volume at −15 °C, m³ | 15 |
| Recommended cold-room volume at −20 °C, m³ | 9 |
| Recommended cold-room volume at −25 °C, m³ | 5 |
| Controls and functions | |
|---|---|
| Controller | XW270K |
| Dimensions and weight | |
|---|---|
| Dimensions according to manufacturer drawing | A=340; B=514; C=122; D=330; E=620; F=920; G=140; H=600; I=335; J=75; K=30; L=522; M=16; N=218 mm |
| Mounting configuration | Wall-mounted Drop-in installation; A–N mounting frame dimensions are not a validated panel cut-out. Confirm the drawing and panel thickness for this model. |
| Weight, kg | 90 |
| Energy and electrical data | |
|---|---|
| Input Power, W | 1090 |
| Maximum current draw, A | 13.4 |
| Voltage / Frequency, V/Hz | 230V I+N ~ 50Hz |
| General information | |
|---|---|
| Delivery method | Made to order; lead time 4–6 weeks |
| Mounting type | Wall-mounted |
| Series | INTARBLOCK A2L CV-NN |
| Refrigeration and ventilation system | |
|---|---|
| Condenser cooling | Air-cooled |
| Defrost Type | Hot-gas defrost |
| Evaporator airflow, m³/h | 800 |
| Noise Level, dB(A) | 35 (at 10 m) |
| Refrigerant | R455A (A2L) |
| Refrigerant Charge, g | less than 1000 |
| Refrigerant GWP | 146 |
| Temperature and performance | |
|---|---|
| Cooling capacity at −15 °C, W | 1303 |
| Cooling capacity at −20 °C, W | 1065 |
| Cooling capacity at −25 °C, W | 848 |
| Temperature group | Negative temperature |