• English
  • Lithuanian
excl VAT

INTARCON BCR-NPD-3068A INTARTOP PRO roof-mounted R290 monoblock, 2107 W

Product code: BCR-NPD-3068A

Available quantity 4-6 weeks

INTARCON INTARTOP PRO BCR-NPD-3068A: roof-mounted R290 for freezer rooms, 2107 W at −20 °C, up to 27 m³ (+35 °C ambient). XM670K, 80–150 mm panels; made to order.
€5,53482 inc VAT
€4,57423 excl VAT
Have any questions about this item? Ask
Manufacturer: INTARCON

INTARCON INTARTOP PRO BCR-NPD-3068A is a roof-mounted R290 monoblock for freezer cold rooms. Its PRO layout emphasizes service accessibility, electronic control and a telescopic roof-panel installation. R290 is an A3-class refrigerant (GWP 0.02).

Cooling capacity and recommended room volume

Room temperatureCooling capacityRecommended room volume
-25 °C1574 W14 m³
-20 °C2107 W27 m³
-15 °C2605 W44 m³

Manufacturer data refer to +35 °C ambient temperature. Volumes are indicative; final sizing requires a project-specific heat-load calculation.

PRO standard equipment

Hermetic compressors, coated microchannel condenser, EC condenser fans, accessible service components, washable filter, hot-gas defrost and stainless-steel drain pan. Separated evaporator and condenser sections support roof-panel installation and maintenance.

XM670K controller: remote digital control and clock-based energy-saving and defrost cycles; up to eight compatible devices can be coordinated when suitable network accessories are installed. A complete communications kit is not assumed in the base configuration.

Installation and dimensions

Telescopic roof mounting for 80–150 mm insulated ceiling panels, size 3; catalog power supply 230V I+N ~ 50Hz (c). A–M references follow the 2026 manufacturer catalog p. 279 drawing. Do not interpret the lettered dimensions as a universal installation cut-out.

Drawing letterDimension
A1227 mm
B1082 mm
C687 mm
D712 mm
E563 mm
F490 mm
G117 mm
H80–150 mm
I4 x Ø13 mm
J1130 mm
K1085 mm
L680 mm
M568 mm

Factory options and ducting

Exhaust ductwork requires the optional centrifugal condenser fan with horizontal or vertical discharge. The standard axial fan is not intended to overcome duct pressure loss. Available options include electrical connector and protection, Master–Slave control and ducting accessories. A circular duct adaptor or backdraft damper requires a compatible fan; check duct resistance and correct configuration before ordering.

Safety and supply

R290 is an A3 flammable refrigerant. Qualified personnel must install and service the equipment under the manufacturer's safety rules. Cold-room construction, installation, commissioning and unloading are not included unless otherwise agreed. Made to order; lead time 4–6 weeks.

Capacity and internal fittings
Capacity Cooling Coldroom Units, m³ 27
Recommended cold-room volume at −15 °C, m³ 44
Recommended cold-room volume at −20 °C, m³ 27
Recommended cold-room volume at −25 °C, m³ 14
Controls and functions
Controller XM670K
Dimensions and weight
Dimensions according to manufacturer drawing A=1227; B=1082; C=687; D=712; E=563; F=490; G=117; H=80–150; I=4 x Ø13; J=1130; K=1085; L=680; M=568
Mounting configuration Telescopic 80–150 mm roof-panel mount; verify p. 279 installation drawing
Weight, kg 150
Energy and electrical data
Input Power, W 2240
Maximum current draw, A 11.9
Voltage / Frequency, V/Hz 230V I+N ~ 50Hz (c)
General information
Delivery method Made to order; lead time 4–6 weeks
Mounting type Roof-mounted
Series INTARTOP PRO (CR-NPD)
Refrigeration and ventilation system
Condenser airflow with centrifugal fan, m³/h 3000
Condenser cooling Air-cooled
Defrost Type Hot-gas defrost
Evaporator airflow, m³/h 2800
Noise Level, dB(A) 44 (at 10 m)
Refrigerant R290 (A3)
Refrigerant Charge, g less than 500 per circuit
Refrigerant GWP 0.02
Temperature and performance
Cooling capacity at −15 °C, W 2605
Cooling capacity at −20 °C, W 2107
Cooling capacity at −25 °C, W 1574
Temperature group Negative temperature

There are no reviews for this product!

Write
Call us