Product code: SBHARG1034
Available quantity 4-6 weeks
IMPAFRI SBHARG1034 is a split system for standard cold rooms. This system separates the indoor evaporator from the heat-rejecting condensing unit, allowing the cold-room layout and outdoor ventilation/service space to be planned independently. The factory-matched package helps coordinate the refrigeration equipment.
This model uses a low-profile (slim) evaporator. Use the temperature-specific ratings in the specification when sizing the room.
Select freezer equipment at the required negative-temperature point and positive-temperature equipment at its actual room setpoint. The catalogue volume is an initial selection estimate. Frequent door openings and warm incoming stock can require more capacity in a room of the same volume.
An axial-fan unit needs unobstructed air intake and discharge. Avoid an enclosed, unventilated recess. Where ducted heat rejection is necessary, select a suitable centrifugal configuration and check its own technical ratings.
Published capacity points for this factory model: −25, −20, −15 °C. In the specification, compare capacity and estimated room volume at the same room temperature. Cooling capacity is not electrical input. Provide internal room dimensions, insulation, ambient temperature, daily product load and incoming temperature, door-opening frequency and the proposed pipe route. An unpublished operating point must not be substituted by a rating at a different temperature.
Other factory configuration available in this card: SBHCRG1034. The selection changes the condensing-unit configuration; use the selected SKU data when comparing equipment.

Supply covers the factory condensing unit, evaporator and range-specific controls. The cold-room enclosure, site copper pipework and insulation, electrical installation and commissioning are planned separately. Pre-charge for 10 m does not itself mean that pipes or all interconnecting cables are supplied.
Manufacturer catalogue, printed p. 265. Range and filter selection guide.
| Capacity and internal fittings | |
|---|---|
| Recommended cold-room volume at −15 °C, m³ | 10 |
| Recommended cold-room volume at −20 °C, m³ | 5.9 |
| Recommended cold-room volume at −25 °C, m³ | 3 |
| Dimensions and weight | |
|---|---|
| Weight, kg | 72 |
| Energy and electrical data | |
|---|---|
| Voltage / Frequency, V/Hz | 230 V-I |
| General information | |
|---|---|
| Delivery method | Made to order; lead time on request |
| Equipment type | Refrigeration system |
| Purpose | Standard cold rooms |
| Series | SBHARG |
| Refrigeration and ventilation system | |
|---|---|
| Complete split kit scope | Condensing unit + evaporator + series controls and refrigeration components |
| Evaporator type | Low-profile (slim) |
| Factory refrigerant pre-charge pipe length, m | 10 |
| Noise Level, dB(A) | 40 (10 m) |
| Refrigerant | R449A |
| Refrigeration system type | Split system |
| Temperature and performance | |
|---|---|
| Cooling capacity at −15 °C, W | 1038 |
| Cooling capacity at −20 °C, W | 858 |
| Cooling capacity at −25 °C, W | 622 |
| Temperature group | Negative temperature |
There are no reviews for this product!